The HEPA filters of the filter class H13 / H14 are used in the supply, exhaust and recirculation filtration of ventilation systems with the highest requirements for clean air and sterility, such as
- in the treatment of hazardous substances (asbestos removal, heavy metals, carcinogenic dusts, cooling lubricants, etc.)
- in demanding air-conditioning technology (operating rooms / intensive care units of hospitals, laboratories, clean rooms, etc.)
- in highly sensitive industrial processes (pharmacy, biotechnology, chemistry, optics, food processing, microelectronics, etc.)
- as a downstream police filter in dedusting technology
Technical data
- Filter media: Highly separating micro-glass fiber paper
- Sealing: Polyurethane, endless and homogeneously foamed
- Filter class: H13 / H14 according to EN 1822:2009
- Filter efficiency H 13: > 99,95% in MPPS leakproof checked (Most Penetrated Particle Size)
- Filter efficiency H 14: > 99,995% in MPPS leakproof checked
- Moisture resistance: 100% (relative humidity)
- Temperature resistance: 70 °C
Dimensions mm | Filter class | Article number | Fold depth mm | Filter surface m² | Weight kg | Flow rate at passed DOP-/DEHS Test* m³/h |
910x610x292 | H 13 | AU1044 | 280 | 46,0 | 15,5 | 6200 |
H 14 | AU3788 | |||||
610x610x292 | H 13 | AU619 | 280 | 32,5 | 9,5 | 5700 |
H14 | AU3575 | 31,0 | ||||
610x305x292 | H 13 | AU1052 | 280 | 15,9 | 8,5 | 3400 |
H 14 | AU3496 | 14,0 | ||||
305x305x292 | H 13 | AU2093 | 280 | 7,5 | 5,0 | 1800 |
H 14 | AU1888 | 6,9 | ||||
305x305x150 | H 13 | AU3663 | 100 | 3,6 | 2,5 | 1100 |
H 14 | AU3664 | 3,0 | ||||
305x305x68 | H 13 | AU1437 | 1,5 | 400 | ||
284x284x150 | H 13 | AU1499 | 100 | 3,0 | 3,0 | 1100 |
* Dop / DEHS test carried out by deconta